Product overview: Fluke 1662 Multifunction Testers

Fluke 1662 Multifunction Installation Tester delivers solid, basic installation testing features

The Fluke 1662 installation tester gives you Fluke reliability and all the basic testing power you need for day-in, day-out installation testing. It tests to all local regulations and is easy and intuitive to use. Additional helpful features like the On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

  • Measures RCD switching time and tripping level (ramp test)
  • Measures trip time and current for RCD type A & AC in one test
  • Measures RCD variable current
  • Provides automatic RCD test sequence
  • Includes Z-max memory for loop tests to support easy evaluation of the highest loop test value
  • Provides unique zero adapter for fast, reliable and accurate test lead and mains cord compensation
  • Includes a phase sequence indicator
  • Comes with hard carrying case, padded carrying and waist strap, and remote control probe and lead

Key features

A solid, reliable, basic installation tester

  • Tests voltage and frequency
  • Checks wiring polarity to detect broken N wires
  • Measures insulation resistance and loop and line resistance
  • Measures motor windings with continuity test
  • Calculates prospective earth fault current (PEFC/IK) and prospective short-circuit current (PSC/IK)

Specifications: Fluke 1662 Multifunction Testers

AC voltage measurement

Range

500 V

Resolution

0.1 V

Accuracy 45 Hz – 66 Hz

0.8% + 3

Input impedance

360 kΩ

Overload protection

660 V rms

Continuity testing (RLO)

Range (autoranging)

20 Ω / 200 Ω / 2000 Ω

Resolution

0.01 Ω / 0.1 Ω / 1 Ω

Open Circuit Voltage

>4 V

Insulation resistance measurement (RISO)

Accuracy of tTest voltage (at rated test current)

+10%, -0%

Test voltage

100 V
250 V
500 V
1000 V

Insulation resistance range

20 MΩ / 50 MΩ
20 MΩ / 100 MΩ
20 MΩ / 200 MΩ
20 MΩ / 200 MΩ / 500 MΩ
20 MΩ / 200 MΩ / 1000 MΩ

Resolution

0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ
0.01 MΩ / 0.1 MΩ / 1 MΩ

Test current

1 mA @ 50 kΩ
1 mA @ 100 kΩ
1 mA @ 250 kΩ
1 mA @ 500 kΩ
1 mA @ 1 MΩ

Loop and line impedance (ZI)

Range

10 Ω / 0.001 Ω / High current mΩ mode

Resolution

0.01 Ω / 0.1 Ω / 1 Ω

Prospective earth fault current, PSC test

Range

1000 A / 10 kA (50 kA)

Resolution

1 A / 0.1 kA

Computation

Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.

RCD testing, RCD types tested

RCD Type

A4, AC¹, G², S³

Notes

¹Responds to AC
²General, no delay
³Time delay
4Responds to pulsed signal
5Responds to smooth DC signal

Tripping speed test (ΔT)

Current settings¹

10-30-100-300-500-1000 mA – VAR
10-30-100 mA

Multiplier

x ½, x 1
x 5

Measurement range

RCD Type G

310 ms
50 ms

RCD Type S

510 ms
160 ms

Notes

¹1000 mA type AC only
700 mA maximum type A in VAR mode
VAR mode not available for type B.

RCD/FI-Tripping Current Measurement/Ramp Test (IΔN)

Current range

30% to 110% of RCD rated current¹

Step size

10% of IΔN²

Dwell time

Type G

300 ms/step

Type S

500 ms/step

Measurement accuracy

±5%

Specified trip current ranges (EN 61008-1)

50% to 100% for Type AC
35% to 140% for Type A (>10 mA)
35% to 200% for Type A (≤10 mA)
50% to 200% for Type B
²5% for Type B

Notes

¹30% to 150% for Type A IΔN > 10 mA
30% to 210% for Type A IΔN = 10 mA
20% to 210% for Type B

Phase Sequence Indication

Icon

 Phase Sequence indicator is active.

General Specifications

Size (L x W x H)

10 x 25 x 12.5 cm

Weight (incl. batteries)

1.3 Kg

Battery size, quantity

Type AA, 6 ea.

Sealing

IP-40

Safety

Complies with EN61010-1 Ed 2.0 (2001-02), UL61010, ANSI/ISA –s82.02.01 2000 and CAN/CSA c22.2 No. 1010 2nd edition

Overvoltage

CAT III / 500V; CAT IV 300V

Performance

EN61557-1 to EN61557-7 Second Edition and EN61557-10 Second Edition

 

 