TRANSFER SWITCH EQUIP MTSE 415V 16A 4P.

Model
product brand name SENTRON
product designation 3KC transfer switching equipment
design of the product manually operated
display version / for switch position indicator door-
coupling rotary operating mechanism
I  ON- O OFF- II ON
design of the operating mechanism Without handle
design of handle without
type of the driving mechanism Front operating mechanism
type of the driving mechanism / motor drive No
General technical data
number of poles 4
type of device fixed mounting
size of switch disconnector 1
I2t value
● with closed switch / for combination switch + fuse / at 500 V / maximum
● with closed switch / at 690 V / for combination switch + gG fuse / maximum
13 300 A²·s
13 700 A²·s
● of the fuse / at 415 V / maximum permissible 26 505 A²·s
● of the fuse / at 500 V / maximum permissible 26 505 A²·s
● of the gG fuse / at 690 V / maximum permissible 24 005 A²·s
● with closed switch / for combination switch + fuse / at 415 V / maximum 13 300 A²·s
mechanical service life (switching cycles) / for
function sequence O-I-O / typical
15,000
position / of the switch operating mechanism in center
overvoltage category III
degree of pollution 3
insulation voltage
● rated value
1 000 V
Supply voltage
operating current / at AC / rated value 16 A
operating voltage
● at AC / at 50/60 Hz / rated value
415 V
Protection class
protection class IP IP20
protection class IP  
● with closed switch / with cover or cable lug IP20
cover  
● on the front IP20
Dissipation
power loss [W]
● with conventional rated thermal current / per pole
● with conventional rated thermal current / per device
● for rated value of the current / at AC / in hot operating state / per pole
0.2 W
0.8 W
0.2 W
● operating current / at AC-23 A / at 690 V / rated
value
16 A
● operating current / at AC-23 A / at 500 V / rated value 16 A
● operating current / at AC-22 A / at 690 V / rated value 16 A
● operating current / at AC-22 A / at 500 V / rated value 16 A
● operating current / at AC-21 / at 690 V / rated value 16 A
● operating current / at AC-21 / at 500 V / rated value 16 A
● operating current / at AC-21 A / at 415 V / rated value
● operating current / at AC-22 A / at 415 V / rated value
● operating current / at AC-23 A / at 415 V / rated value
● operating current / at AC-31 B / at 415 V / rated value
● operating current / at AC-32 B / at 415 V / rated value
● operating current / at AC-33 B / at 415 V / rated value
● operating current / at AC-33 iB / at 415 V / rated value
● operating current / at AC-35 B / at 400 V / rated value
16 A
16 A
16 A
16 A
16 A
16 A
16 A
16 A
continuous current
● rated value
● at 40 °C / rated value
● at 45 °C / rated value
● at 50 °C / rated value
● at 55 °C / rated value
● at 60 °C / rated value
● at 65 °C / rated value
● at 70 °C / rated value
16 A
16 A
16 A
16 A
16 A
16 A
16 A
16 A
operating current / of upstream fuse / rated value 63 A
let-through current / of the fuse / at 500 V / maximum
permissible
8 135 A
let-through current / of the gG fuse / at 690 V /
maximum permissible
8 805 A
let-through current / with closed switch
● at 690 V / for combination switch + gG fuse / maximum permissible
● for combination switch + fuse / at 500 V / maximum permissible
7 500 A
7 000 A
Main circuit
operating power
● at AC-23 A / at 400 V / at 50/60 Hz / rated value
● at AC-23 A / at 500 V / rated value
● at AC-23 A / at 690 V / at 50/60 Hz / rated value
7.5 kW
7.5 kW 11 kW
operating current / rated value 16 A
Auxiliary circuit
number of connected NC contacts / for auxiliary
contacts
0
number of connected NO contacts / for auxiliary
contacts
0
number of connected CO contacts / for auxiliary
contacts
0
number of CO contacts / for auxiliary contacts 8
number of NC contacts / for auxiliary contacts 0
number of NO contacts / for auxiliary contacts 0
suitability for use
● main switch
● switch disconnector
● EMERGENCY OFF switch
● safety switch
● maintenance/repair switch
Yes Yes Yes Yes Yes
product feature / interlock No
product extension / auxiliary switch Yes
product extension / optional
● motor drive
● voltage trigger
No No
Short circuit
short-circuit current making capacity (Icm) / for switch
disconnector
● at AC 415 V / without fuse link / acc. to IEC 60947-6-1 / rated value / minimum
● at AC 690 V / without fuse link / acc. to IEC 60947-3 / rated value / minimum
7.7 kA 7 kA
conditional short-circuit current / with line-side fuse
protection
 
● at 415 V / by gG fuse / acc. to IEC 60947-6-1 / rated value 100 kA
● at 415 V / by gG fuse / rated value 100 kA
● at 500 V / by gG fuse / acc. to IEC 60947-3 / rated value 100 kA
● at 690 V / by gG fuse / acc. to IEC 60947-3 / rated value 100 kA
Connections
type of connectable conductor cross-sections / with flexible busbar 2x (0.8x9  mm²)
type of connectable conductor cross-sections
● for copper busbar
1x (2x9 mm²)
type of connectable conductor cross-sections / for
copper conductor
 
● solid
● finely stranded / with core end processing
● stranded
1x (1 ... 16 mm²)
1x (1 ... 35 mm²)
1x (6 ... 35 mm²)
type of electrical connection
● for main current circuit
box terminal
Mechanical Design
height 119 mm
width 237.6 mm
depth 84.5 mm
mounting type Screw fixing and standard rail mounting 35 mm
mounting type
● front mounting with 4-hole attachment
● front mounting with central attachment
● rail mounting
No No Yes
mounting position any
net weight 1 700 g
Environmental conditions
ambient temperature / during operation
● minimum
● maximum
-25 °C
70 °C
ambient temperature / during storage
● minimum
● maximum
-50 °C
80 °C