Description
TRANSFER SWITCH EQUIP MTSE 415V 160A 4P
Model | |||||||||||||||||||
product brand name | SENTRON | ||||||||||||||||||
product designation | 3KC transfer switching equipment | ||||||||||||||||||
design of the product | manually operated | ||||||||||||||||||
display version / for switch position indicator door- coupling rotary operating mechanism |
I ON- O OFF- II ON | ||||||||||||||||||
design of the operating mechanism | Without handle | ||||||||||||||||||
design of handle | without | ||||||||||||||||||
type of the driving mechanism | Front operating mechanism | ||||||||||||||||||
type of the driving mechanism / motor drive | No | ||||||||||||||||||
General technical data | |||||||||||||||||||
number of poles | 4 | ||||||||||||||||||
type of device | fixed mounting | ||||||||||||||||||
size of switch disconnector | 2 | ||||||||||||||||||
I2t value ● with closed switch / for combination switch + fuse / at 500 V / maximum ● with closed switch / at 690 V / for combination switch + gG fuse / maximum |
135 600 A²·s 178 300 A²·s |
||||||||||||||||||
● with closed switch / at 690 V / for combination switch + aM fuse / maximum |
201 200 A²·s | ||||||||||||||||||
● of the fuse / at 415 V / maximum permissible | 223 005 A²·s | ||||||||||||||||||
● of the fuse / at 500 V / maximum permissible | 223 005 A²·s | ||||||||||||||||||
● of the gG fuse / at 690 V / maximum permissible | 226 005 A²·s | ||||||||||||||||||
● of the aM fuse / at 690 V / maximum permissible | 235 000 A²·s | ||||||||||||||||||
● with closed switch / for combination switch + fuse / at 415 V / maximum | 135 600 A²·s | ||||||||||||||||||
mechanical service life (switching cycles) / for function sequence O-I-O / typical |
15,000 | ||||||||||||||||||
position / of the switch operating mechanism | in center | ||||||||||||||||||
overvoltage category | III | ||||||||||||||||||
degree of pollution | 3 | ||||||||||||||||||
insulation voltage ● rated value |
1 000 V | ||||||||||||||||||
Supply voltage | |||||||||||||||||||
operating current / at AC / rated value | 160 A | ||||||||||||||||||
operating voltage ● at AC / at 50/60 Hz / rated value |
415 V | ||||||||||||||||||
Protection class | |||||||||||||||||||
protection class IP | IP20 | ||||||||||||||||||
protection class IP | |||||||||||||||||||
● with closed switch / with cover or cable lug | IP20 | ||||||||||||||||||
cover | |||||||||||||||||||
● on the front | IP20 | ||||||||||||||||||
Dissipation | |||||||||||||||||||
power loss [W] ● with conventional rated thermal current / per pole ● with conventional rated thermal current / per device ● for rated value of the current / at AC / in hot operating state / per pole |
7 W 28 W 7 W |
||||||||||||||||||
● operating current / at AC-23 A / at 690 V / rated value |
125 A | ||||||||||||||||||
● operating current / at AC-23 A / at 500 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-22 A / at 690 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-22 A / at 500 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-21 / at 690 V / rated value |
160 A | ||||||||||||||||||
● operating current / at AC-21 / at 500 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-21 A / at 415 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-22 A / at 415 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-23 A / at 415 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-31 B / at 415 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-32 B / at 415 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-33 B / at 415 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-33 iB / at 415 V / rated value | 160 A | ||||||||||||||||||
● operating current / at AC-35 B / at 400 V / rated value | 160 A | ||||||||||||||||||
continuous current | |||||||||||||||||||
● rated value | 160 A | ||||||||||||||||||
● at 40 °C / rated value | 160 A | ||||||||||||||||||
● at 45 °C / rated value | 160 A | ||||||||||||||||||
● at 50 °C / rated value | 160 A | ||||||||||||||||||
● at 55 °C / rated value | 160 A | ||||||||||||||||||
● at 60 °C / rated value | 160 A | ||||||||||||||||||
● at 65 °C / rated value | 160 A | ||||||||||||||||||
● at 70 °C / rated value | 160 A | ||||||||||||||||||
operating current / of upstream fuse / rated value | 160 A | ||||||||||||||||||
let-through current / of the fuse / at 500 V / maximum permissible |
18 005 A | ||||||||||||||||||
let-through current / of the gG fuse / at 690 V / maximum permissible |
16 005 A | ||||||||||||||||||
let-through current / of the aM fuse / at 690 V / maximum permissible |
16 700 A | ||||||||||||||||||
let-through current / with closed switch | |||||||||||||||||||
● at 690 V / for combination switch + aM fuse / | 17 600 A | ||||||||||||||||||
maximum permissible | |||||||||||||||||||
● at 690 V / for combination switch + gG fuse / | 18 700 A | ||||||||||||||||||
maximum permissible | |||||||||||||||||||
● for combination switch + fuse / at 500 V / | 17 900 A | ||||||||||||||||||
maximum permissible | |||||||||||||||||||
Main circuit | |||||||||||||||||||
operating power ● at AC-23 A / at 400 V / at 50/60 Hz / rated value ● at AC-23 A / at 500 V / rated value ● at AC-23 A / at 690 V / at 50/60 Hz / rated value |
90 kW 110 kW 110 kW |
||||||||||||||||||
operating current / rated value | 160 A | ||||||||||||||||||
Auxiliary circuit | |||||||||||||||||||
number of connected NC contacts / for auxiliary contacts |
0 | ||||||||||||||||||
number of connected NO contacts / for auxiliary contacts |
0 | ||||||||||||||||||
number of connected CO contacts / for auxiliary contacts |
0 | ||||||||||||||||||
number of CO contacts / for auxiliary contacts | 8 | ||||||||||||||||||
number of NC contacts / for auxiliary contacts | 0 | ||||||||||||||||||
number of NO contacts / for auxiliary contacts | 0 | ||||||||||||||||||
suitability for use ● main switch ● switch disconnector ● EMERGENCY OFF switch ● safety switch ● maintenance/repair switch |
Yes Yes Yes Yes Yes | ||||||||||||||||||
product feature / interlock | No | ||||||||||||||||||
product extension / auxiliary switch | Yes | ||||||||||||||||||
product extension / optional ● motor drive ● voltage trigger |
No No | ||||||||||||||||||
Short circuit | |||||||||||||||||||
short-circuit current making capacity (Icm) / for switch disconnector ● at AC 415 V / without fuse link / acc. to IEC 60947-6-1 / rated value / minimum ● at AC 690 V / without fuse link / acc. to IEC 60947-3 / rated value / minimum |
17 kA 12 kA |
||||||||||||||||||
conditional short-circuit current / with line-side fuse protection |
|||||||||||||||||||
● at 415 V / by gG fuse / acc. to IEC 60947-6-1 / rated value | 100 kA | ||||||||||||||||||
● at 415 V / by gG fuse / rated value | 100 kA | ||||||||||||||||||
● at 500 V / by gG fuse / acc. to IEC 60947-3 / rated value | 100 kA | ||||||||||||||||||
● at 690 V / by gG fuse / acc. to IEC 60947-3 / rated value | 65 kA | ||||||||||||||||||
Connections | |||||||||||||||||||
type of connectable conductor cross-sections / with flexible busbar |
3x (0.8x14 mm²) | ||||||||||||||||||
type of connectable conductor cross-sections ● for copper busbar |
1x (3x14 mm²) | ||||||||||||||||||
type of connectable conductor cross-sections / for copper conductor ● solid ● finely stranded / with core end processing ● stranded |
1x (2.5 ... 16 mm²) 1x (2.5 ... 70 mm²) 1x (10 ... 70 mm²) |
||||||||||||||||||
type of electrical connection ● for main current circuit |
box terminal | ||||||||||||||||||
Mechanical Design | |||||||||||||||||||
height | 126 mm | ||||||||||||||||||
width | 309.6 mm | ||||||||||||||||||
depth | 84.5 mm | ||||||||||||||||||
mounting type | Screw fixing and standard rail mounting 35 mm | ||||||||||||||||||
mounting type ● front mounting with 4-hole attachment ● front mounting with central attachment ● rail mounting |
No No Yes | ||||||||||||||||||
mounting position | any | ||||||||||||||||||
net weight | 2 650 g | ||||||||||||||||||
Environmental conditions | |||||||||||||||||||
ambient temperature / during operation ● minimum ● maximum |
-25 °C 70 °C |
||||||||||||||||||
ambient temperature / during storage ● minimum ● maximum |
-50 °C 80 °C |
Payment & Security