Description
eSys LRD thermal overload relay, 6A/690V, thermal setting range 4-6A, tripping class 10A, for protection of 3-phase motors 2.2kW@400V.
A differential device with phase failure and load unbalance detection.
It provides a thermal adjustment dial, a manual-automatic reset selector, a test selector for simulation of tripping, reset and stop buttons, a flag indicator, and 2 auxiliary contacts 1NO+1NC for fault signaling.
Settings are protected by a transparent cover lockable by sealing. Connection by screw clamp terminals,
it connects directly to the bottom terminals of 3-pole contactors LC1D09-D38. Mounting on DIN rail or screw fixing, separated from the contactor, with the use of a terminal block LAD7B106 (to be ordered separately).
Multi standards certified (IEC, UL, CSA, CCC, EAC, ATEX, Marine), Green Premium compliant (RoHs/Reach).
| SKU | MAS03071LRD10 |
|---|---|
| Weight (kg) | 0.124000 |
| Manufacturer | Schneider Electric |
| Model Number | LRD10 |
| Warranty | 18 Months |
| Product Certification | RINA CCC GOST DNV LROS (Lloyds register of shipping) UL CSA BV ATEX INERIS GL |
| Mercury Free | Yes |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient Air Temperature for Operation | -20·0 ?C without derating conforming to IEC 60947-4-1 |
| Range | 4...6 A |
| Relay Application | Motor protection |
| Product Compatibility | LC1D25 LC1D38 LC1D12 LC1D09 LC1D18 LC1D32 |
| thermal protection adjustment range | 4...6 A |
| Thermal overload class | Class 10A |
| phase failure sensitivity | Tripping current 130 % of Ir on two phase |
| temperature compensation | -20·0 ?C |
| net weight | 0.124 Kg |