Description
Schneider Electric MCCB - EasyPact EZC, EZC250N4200, 200A, 25kA, 4Pole MCCB
| range of product |
EasyPact
|
|
|---|---|---|
| product or component type |
Circuit breaker
|
|
| device short name |
Easypact EZC250N
|
|
| circuit breaker name |
Easypact EZC250N
|
|
| device application |
Distribution
|
|
| poles description |
4P
|
|
| protected poles description |
3t
|
|
| network type |
DC
AC |
|
| network frequency |
50/60 Hz
|
|
| [In] rated current |
250 A at 40 °C
|
|
| [Ui] rated insulation voltage |
690 V AC 50/60 Hz conforming to IEC 60947-2
|
|
| [Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-2
|
|
| [Ue] rated operational voltage |
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2 |
|
| breaking capacity code |
N
|
|
| breaking capacity |
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| [Ics] rated service breaking capacity |
10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 125 V DC conforming to IEC 60947-2 10 kA at 250 V DC conforming to IEC 60947-2 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 |
|
| suitability for isolation |
Yes conforming to IEC 60947-2
|
|
| utilisation category |
Category A
|
|
| trip unit name |
TM-D
|
|
| trip unit technology |
Thermal-magnetic
|
|
| trip unit rating |
200 A at 50 °C
|
|
| protection type |
Short-circuit protection
Overload protection |
|
| pollution degree |
3 conforming to IEC 60947
|
| control type |
Toggle
|
|
|---|---|---|
| mounting mode |
Fixed
|
|
| mounting support |
Backplate
|
|
| upside connection |
Front
|
|
| downside connection |
Front
|
|
| mechanical durability |
10000 cycles
|
|
| electrical durability |
Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
|
|
| connection pitch |
35 mm
|
|
| local signalling |
Positive contact indication
|
|
| neutral protection setting |
Without protection
|
|
| earth-leakage protection |
Without
|
|
| height |
165 mm
|
|
| width |
140 mm
|
|
| depth |
60 mm
|
| standards |
JIS C8201-2-2
EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2 |
|
|---|---|---|
| IP degree of protection |
IP20 conforming to IEC 60529
|
|
| IK degree of protection |
IK07 conforming to EN 50102
|
|
| ambient air temperature for operation |
-25…70 °C
|
|
| ambient air temperature for storage |
-35…85 °C
|